Abstract

In the present study, a membrane-based air-to-air planar humidifier (MAPH) with baffle-blocked flow channels and a common MAPH are fabricated, tested and compared. These MAPHs are well thermal insulated from their surroundings. Polyoxymethylene (POM) plates with some unique properties such as large tensile and flexural strength, high chemical resistance and high stiffness are used to create channels at dry and humid sides of MAPHs. The obtained findings revealed that the higher heat and water transfer rates and smaller dew point approach temperature (DPAT) in entire tested flow rates occurs in baffle-blocked MAPH. To evaluate the MAPH performance with considering the pressure drop, a dimensionless parameter, performance evaluation criteria (PEC), is introduced. At flow rates less than 1 m3/h, PEC is less than 1, indicating a decline in MAPH performance with considering the pressure drop. In baffle-blocked MAPH using water trap in the inlet of dry side leads to the performance deterioration. Additionally, the increased relative humidity (RH) of humid side inlet causes an increase in DPAT, consequently, the performance deterioration.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.