Abstract

In this study, the thermal impact of defrost cycle of both residential heat and energy recovery ventilators (HRV and ERV) was investigated using TRNSYS. The thermal efficiency patterns of the units were obtained from winter experiments, and then implemented into the existing HRV and ERV models for simulations in the context of airtight environment. Throughout the heating season, the minimum humidity of the airtight house was increased due to the reintroduction of humid indoor air/melted frost. For the HRV, simulation results indicated that its yearly demand of defrost cycle was 3.5 times higher the ERV. In other words, the HRV used in cold days could significantly deteriorate indoor air quality, which contradicted the main purpose of mechanical ventilation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.