Abstract

The feasibility of a novel total energy recovery ventilator (HERV) was studied, through the use of an Excel-based screening tool developed for cost analysis, and through TRNSYS simulations for performance analysis. Cost analysis indicated that the HERV almost always outperformed the conventional systems, whereas its attractiveness could be limited by its high capital investment. Simulation results indicated that the counter-flow HERV provided better control of house humidity towards the setpoint, in the meantime, minimized the annual energy use. The performance of heat recovery (HRV) and energy recovery (ERV) ventilators was investigated side-by-side at the Archetype Sustainable Twins-House located in Toronto, Canada. The ERV sensible efficiency ranged from 76.4% to78.5% at an outdoor temperature of -20°C and 5°C respectively, while the HRV efficiency ranged from 91.0% to 95.0% at -16.6°C and 0.7°C respectively. Freezing caused a dramatic drop in the efficiency that was found to be as low as 50%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.