Abstract

The retrofitting of existing public buildings to save energy and reduce carbon emissions is a priority for China’s building sector. Accordingly, the Chinese government requires all public buildings to be energy retrofitted based on the Design Standard for Energy Efficiency of Public Buildings GB50189-2015. However, few studies have been conducted to assess the energy efficiency of this design standard in the hot summer and cold winter (HSCW) climate region of China. The aim of this study was therefore to provide sensitivity analysis for the thermal properties of the envelope of a typical public building energy retrofit in China’s HSCW climate region. The results show that the thermal performance of the existing envelope of the sample building was very poor, with heating and cooling energy consumption 18.94% higher than the GB90189-2015 baseline model. It was found that better optimized parameters could reduce the heating and cooling energy load by 28.26% compared with the parameters of the sample building. The findings from this study provide valuable references for local governments and practitioners eager to improve the energy efficiency of existing public buildings in China’s HSCW region.