Abstract
In this paper, the azeotropic mixture of CO2/R170 (0.78/0.22, mass fraction) is presented as a refrigerant to replace R134a in an ASHPWH system. On the basis of the first and second laws of thermodynamics, system performance and the exergy efficiency analysis are carried out for the system using both refrigerants. The results show that both the COPheat (coefficient of heating performance) and exergy efficiency of the system using the CO2/R170 mixture refrigerant are higher than that using the R134a, and the values can be increased by 31.3% and 30.6%, respectively. Moreover, the compressor discharge temperature for CO2/R170 is about 34.3–49.8 °C lower and the compression ratio of compressor also has a significant reduction (from 12.0417 to 3.2734), which leads to a higher lifetime for the compressors. So, the CO2/R170 mixture may be a good choice to substitute for R134a in ASHPWH systems. Also, a CO2/R170 ASHPWH system may be more suitable in cold region.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.