Abstract
Abstract In this study, the performance of a two-stage compression transcritical cycle with an expander (TCE) and a conventional single-stage compression transcritical cycle with a throttling valve (SCT) using pure CO2 and CO2/ethane (0.78/0.22, mass fraction) azeotropy mixture as a refrigerant in an air-source heat pump water heater (ASHPWH) system is investigated. From the point of the first and second laws of thermodynamics, the theoretical analysis of cycle characteristics based on the two systems with both refrigerants are carried out and compared in detail. The results show that the COP of TCE cycle with CO2 and CO2/ ethane are at least 57.4% and 81.6% higher than those of the SCT cycle under the studied conditions. The main attractiveness of the CO2/ethane azeotropy refrigerant is connected with its lower discharge temperature compared with the pure CO2, which can prolong the compressor lifetime. In addition, the CO2/ethane azeotropy refrigerant can obviously reduce the evaporation temperature, which is conducive to the ASHPWH system in cold region.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.