Abstract
Desiccant cooling system is a suitable alternative option for conventional cooling system in humid climates. It is an environmental protection technique for cooling buildings. This study has investigated the effect of supply/regeneration section area ratio on the performance of desiccant wheels in hot and humid climates, using Silica Gel (WSG) and Molecular Sieve (LT3) desiccants. To this end, some parameters such as outlet air humidity ratio, process removed moisture, process outlet temperature, reactivation outlet temperature and reactivation outlet moisture have been examined as a function of rotational speed and inlet air humidity ratio in 1:3, 1:2 and 1:1 split. In this study, desiccant materials are regenerated using a constant regeneration temperature of 80 °C, wheel rotation speed range of 4–12 RPH (revolutions per hour) and variable humidity. The results show that a rise in area ratio causes an increase in process removed moisture, process outlet temperature, reactivation outlet temperature and a drop in reactivation outlet moisture and outlet humidity ratio of process air.