Abstract

In order to improve the economy of operation of transformer, this study presents a strategy to ensure the safety of power transformer for the situation of overload operation of parallel transformer. According to the variation of actual transformer operation, the authors divide the daily load curve into two typical time periods. In the high load operation period, except the constraint of minimum power loss for the economic operation, the factor for hot-spot temperature rise of the transformer should also be considered, so that an economic operation mode and parallel switching time could be obtained. This strategy estimates the hot spot temperature by the finite difference method, and obtains the optimal switching time through binary searching, according to the environment temperature and load curve. The analysis of the example of the operation of two sets of three winding transformers in parallel with different capacity shows that the method of optimization of the operation could reduce the loss. In the meantime, it could ensure the operation safety of the transformer, and prolong the service life of transformer.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.