Abstract
This paper presents a model of double-ring type grounding pole unequal depth embedding for high-voltage direct current (HVDC) transmission system; and introduces calculation formula of DC ground potential distribution when double-ring type grounding pole is unequal buried. Furthermore the ground potential distribution and stride voltage level around the grounding pole and influence of grounding depth and soil parameters on the current field are discussed in this paper. The electric field zoning model of the ring current source is established by using the power system grounding pole analysis software CDEGS to verify the feasibility of this method. As the model is able to make the grounding current overflow density and potential distribution as uniform as possible, there is no serious local current concentration.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Earth and Environmental Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.