Abstract

The ability to diagnose the integrity of the transformer windings and core through online diagnostic method would be useful for electric utilities who are concerned about the availability and reliability of power transformer. This paper presents results of a study to identify the condition of power transformer windings and core by measuring the vibration signal of outdoor transformer in normal operating conditions. The obtained vibration signal which is recorded from various places on the transformer tank is analyzed by matching the signal frequency spectrum with transformer load. From this study, mechanical integrity of windings and core inside the transformer is determined by comparing the correlation between each main frequency of vibration signal and the load among similar transformer.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.