Abstract

Performance of Photovoltaic-double skin façade (Photovoltaic-DSF) system in summer has been critical. Owing to high solar ingress, cooling requirement of a building significantly increases. Photovoltaic-DSF system provides a shield and controls the heat gain through fenestration in the interior spaces. In the present article, mathematical correlations are developed to analyse energy behaviour of forced-ventilated Photovoltaic-DSF system in India’s hot summer zone, that is, Jaipur. The Photovoltaic-DSF system has been installed and monitored for Jaipur’s summer months (May to July). L25 Orthogonal array of design parameters (air cavity thickness, air velocity and PV panel’s transparency) and their respective levels have been developed using Taguchi design to perform experiments. Based on experimental results, multiple linear regression has been used to forecast solar heat gain coefficient, PVs electrical power and daylighting illuminance indoors as function of design factors. The statistical significance of mathematical relationships is supported by variance analysis, which is found to be in good accord with field measurements ( R2 > 0.90). The proposed correlations are pragmatic in designing Photovoltaic-DSF systems for hot summer conditions. The Photovoltaic-DSF system with 30% transmittance and air velocity of 5 m/s in 200 mm air cavity thickness achieved maximum energy performance in hot summers.