Abstract

This study aims to design the optimum heat pipe heat exchanger (HPHE) to recover heat from flue gas of boiler for increasing the temperature of feed water. The optimum thermosyphon heat exchanger sizing was simulated on the basis of thermo-economical method and simulation program was construct by using the MATLAB 2021b. The program was simulated by input physical parameters of the thermosyphon and heat exchanger and the thermoeconomic parameters. It was found that R134a was chosen as the working fluid of this study. In addition, the optimum of number of tubes, heat transfer rate and the optimized effectiveness of HPHE were 87 tubes, 4,873 W and 0.237, respectively. Moreover, the net saving and payback period of this HPHE were 14,865 USD and 310 days, respectively.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.