Abstract
The heating, ventilation, and air conditioning (HVAC) system plays a crucial role in ensuring the safety of workers and preventing the release of gaseous radioactive materials into the environment during the decommissioning of a nuclear power plant (NPP). To establish an HVAC operation strategy, decommissioning phases were divided into four stages, and the HVAC systems were reclassified. In addition, assumptions have been made regarding design modifications and maintenance for the reactor containment building (RCB) HVAC, fuel handling building (FHB) HVAC, and main control room (MCR) HVAC. Based on these, for RCB HVAC operation, natural ventilation and RCB purge operation during the transition period are proposed. In the decommissioning stage, recirculation operation, entire ventilation operation consisting of continuous operation and purge operation, and finally partial ventilation operation to purify local space were proposed. Moreover, during the transition period, the FHB HVAC was proposed to operate as normal NPP, and the MCR HVAC was suggested to operate with safety-related equipment removed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.