Abstract
In the first part of the paper, a new approach to the reduction of large dynamic network models is presented. This method is implemented in the program package PSD and is used here in an exemplary fashion to reduce the model of the European power system to a model usable for the solution of a number of problems. In the second part, the paper describes a new damping concept of inter-area oscillations in large power systems. Additionally installed second-level damping controllers are acting on the voltage regulator reference inputs of selected generators. They are using global information about the swing profiles of the inter-area oscillations to be damped. The damping controllers are designed as a H∞-norm optimal decentral control system based on both a topological and a frequency range decomposition of the control task. The solution is demonstrated for the reduced model of the European system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Electrical Engineering (Archiv fur Elektrotechnik)
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.