Abstract
In the European power system UCPTE in parallel operation with the Central-European power systems, called CENTREL, slowly damped inter-area oscillations have been observed. The swings occurred especially when long distance power transactions were carried out. The paper presents results of a small signal stability analysis, focused on power transits in the European power system. In a detailed model the critical swing modes, their mode shapes and the participation factors were investigated. In the East-West-direction two swing modes with wide area effect are significant. To make clear the causes for insufficient damped interarea swings a sensibility analysis relating to power transits, network voltage level and generator voltage controller gains has been carried out.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.