Abstract

Corrugated web profiles are generally used in single story long span structures though there exists limited number of researches about the performance of the connections. Besides there is a rising demand for utilization of corrugated web profiles in construction of low-rise moment resisting frames. This paper aims to evaluate the behaviours of two distinct types of beam-to-column connections namely; i. Conventional types: thick flat plate is used in the panel zone and its near-vicinity, ii. Alternative types: single or double stiffeners are used at both faces in the corrugated-web panel zone. The latter provides key advantages particularly for fabrication. The full scale beam-to-column connections were tested in the Structural and Earthquake Engineering Laboratory of Istanbul Technical University (ITU). In comparing the stiffness and strength characteristics of the tested connections, single and double diagonally-stiffened connections exhibited comparable behaviour to the specimens with flat plate panel zones. The finite element models of all the tested connections were produced with ABAQUS. The analytical results are in good agreement up to an inter-story drift angle of 0.04rad with the experimental ones.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.