Abstract

In this paper, a control strategy for operation of rotor side converter (RSC) of Doubly Fed Induction Generators (DFIG) is developed by injecting reactive power into the grid in order to support the grid voltage during and after grid fault events. The novel nonlinear control method is based on differential geometry theory, and exact feedback linearization is applied for control system design of DFIG. Then the optimal control for the linearized system is obtained through introducing the linear quadratic regulator (LQR) design method. Simulation results on a single machine infinite bus power system show that the proposed nonlinear control method can inject reactive power to fault grid rapidly, reduce the oscillation of active power and improve the transient stability of power system.