Abstract

This paper takes the nuclear power plant power distribution cabinet fire as example and adopts FPRA methodology to analyse the failure probability of cable insulation at contiguous region among distribution cabinet. The influential factor that fire brigade dealt with the fire in the spot is considered in this research. The cumulative distribution function of fire brigade’s arriving and extinguishing time is conducted discretization, confirming the sample statistics of areas and establishing the numbers of cable insulation failure events of distribution cabinet fire. Combining failure predicted model of cable insulation and calculating the failure situation of cable insulation under each of fire background, obtaining the probability that cable insulation failure events among the distribution cabinet fires. The results show that the HRRmax of distribution cabinet fire in term of case scenario is 750 kW, the cable never happens the insulation failure; when the distribution cabinet fire is 1000 kW, the possibility of cable insulation failure is 12.6%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.