Abstract

For more than two decades of Sulphur Hexafluoride (SF6) gases is used as a gas insulation in high voltage equipment especially in substations. In addition to getting an advantage as an insulating gas. SF6 gas is recognized as one of the greenhouse effect gases that cause global warming. Under the Kyoto Protocol, SF6 gas is one of those gases whose use is restricted and gradually reduced to the presence of a replacement gas for SF6 gas. One of the alternative gas alternatives which have the potential of replacing SF6 gas as an insulating gas in Gas Insulated Switchgear (GIS) equipment in the substation is Dichlorotrifluoroethane (CF3CHCl2) gas. The purpose of this paper is to enable a comparison of breakdown voltage with high voltage test and method of calculating Bonding energy to Dichlorotrifluoroethane gas as substitute gas for SF6 gas. At 0.1 bar gas pressure obtained an average breakdown voltage of 18.68 kV / mm at 25oC chamber temperature and has the highest breakdown voltage at 50oC with a breakdown voltage of 19.56 kV / mm. The CF3CHCl2 gas has great potential as an insulating gas because it has more insulation ability high of SF6 gas, and is part of the gas recommended under the Kyoto Protocol. Gas CF3CHCl2 has the capacity to double the value of electronegativity greater than SF6 gas as a major requirement of gas isolation and has a value of Global Warming Potential (GWP) and Ozone Depleting lower than from SF6 gas.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.