Abstract
Abstract — Sulfur hexafluoride gas according to the Montreal Protocol and Kyoto protocol needs to be limited and gradually reduced because it causes global warming, the greenhouse effect and acid rain on the environment. The Kyoto protocol recommends the use of dichlorotrifluoroethane gas as one of the alternatives to substitute sulfur hexafluoride gas. This research discusses the use of dichlorotrifluoroethane gas mixed with CO 2 gas which was known to be able to withstand the breakdown voltage of 592-870 kV. Comparing to breakdown voltage predictions using methods based on bond energy, Paschen's law and high voltage tests. Breakdown voltage deviations using bond energy were better than Paschen's law. The dichlorotrifluoroethane gas economy has a price of 5.18 times cheaper than hexafluoride sulfur gas. The ability of dichlorotrifluoroethane gas to insulation gas in gas insulated switchgear needs to be applied as a real potential substitute for sulfur hexafluoride gas. Keywords- Sulfur Hexafluoride, dichlorotrifluoroethane, bond energy, Paschen’s law, Techno-economy, Gas Insulated Switchgear
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.