Abstract

This paper reports on typical reactor trip setpoints which established for the reactor protection system may be unduly restrictive, depending on how the uncertainties are handled in the plant safety analyses. The current deterministic approaches to establishing specific setpoints contain a substantial amount of conservatism, which can be reduced through the use of a statistical combination of uncertainties process. Using this approach for Three Mile Island Unit 1 indicates that the flux/flow trip setpoint can be relaxed to 1.1 from the existing technical specification value of 1.08. This provides an increased plant operating margin and reduction in the probability of spurious scrams.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.