Abstract

The trip setpoints for the reactor protection system of a 65-MWt advanced integral reactor have been analyzed through sensitivity evaluations by using the Transients and Setpoint Simulation/System-integrated Modular Reactor code. In the analysis, an inadvertent control rod withdrawal event has been considered as an initiating event because this event results in the worst consequences from the viewpoint of the minimum critical heat flux ratio and its consequences are considerably affected by the trip setpoints. Sensitivity evaluations have been performed by changing the trip setpoints for the ceiling of a variable overpower trip (VOPT) function and the pressure of a high pressurizer pressure trip function. Analysis results show that a VOPT function is an effective means to satisfy the acceptance criteria as the control rod rapidly withdraws: on the other hand, a high pressurizer pressure trip function is an essential measure to preserve the safety margin in the case of a slow withdrawal of the control rod because a reactor trip by a VOPT function does not occur in this case. It is also shown that the adoptions of 122.2% of the rated core power and 16.25 MPa as the trip setpoint for the ceiling of a VOPT function and the pressure of a high pressurizer pressure trip function are good selections to satisfy the acceptance criteria.