Abstract

This study discusses the measurement of Partial Discharge (PD) in air insulation. Partial Discharge Measurement is very important to know the condition of electrical equipment. The cause of partial discharge is not only old equipment, but also from set-up errors and insulation problems. In this research partial discharge measurement was performed by using electrical methods. Electrical method use RC Detector. The modeling of partial discharge was done by using needle-plane electrode distant 1 cm in air insulation. Partial discharge measurement parameters include the measurement of Background Noise (BGN), Partial Discharge Inception Voltage (PDIV) and PD Waveform. The Partial Discharge measurement result show that Vpp of BGN ON is higher than Vpp of BGN OFF. The negative PDIV signal first appeared for the RC Detector at a voltage 3.55 KV and Positive PDIV at 4.01 KV. Negative and positive PD waveform for RC Detector at 5 KV, 5.5 KV, 6 KV, 6.5 KV and 7 KV respectively, it has been found that the fall time is greater than the rise time, and peak to peak voltage (Vpp) will be greater when the applied voltage is greater.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.