Abstract
Active power backflow is a unique problem of three-phase isolated cascaded H-bridge (CHB) PV inverter during asymmetric grid voltage fault, resulting in the continuous rise of H-bridge dc-bus voltages and that the inverter will be eventually shut down and off-grid due to voltage out of control. The existing methods are able to completely suppress the active power backflow during single-phase short-circuit fault and two-phase short-circuit fault, but fails in a large operating zone when inter-phase short-circuit fault occurs. For this issue, this paper proposes a novel multiple specific harmonic voltages injection method based on the existing fundamental-frequency zero-sequence voltage compensation strategy, which calculates and injects the optimal third, fifth, seventh and ninth harmonic voltage according to the fault type, drop depth and the normalized power, for minimizing the amplitude of three-phase modulation voltages and then significantly shrinking active power backflow zone of three-phase isolated CHB PV inverter. Then, the area of the active power backflow zones for different control methods is quantitatively calculated and compared by adopting the polynomial fitting to show the advantages of the proposed method. Finally, experimental results are achieved by a low voltage and low power experimental prototype to verify its effectiveness and feasibility.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.