Abstract
Conventional relays fail to detect the high impedance fault (HIF) in distribution lines, as the change in the current magnitude is very negligible compared to conventional relay settings. Moreover, the incorporation of distributed generators in the distribution lines changes the fault current level, which makes the HIF-detection more complex. In this paper, a fuzzy-based intelligent fault detection and classification scheme is developed for the distribution lines integrated with DGs. Two different fuzzy inference systems (FIS) are modelled in each phase to detect the fault. The first FIS identifies the high magnitude of fault current associated with normal shunt faults; and the second FIS identifies the small magnitude of current owing to occurrence of HIF. The proposed scheme uses the features extracted from the Teager energy operator. An extensive study is conducted and the response time is found to be around ¼-1 cycle. Results validate the efficacy of the proposed scheme.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.