Abstract
This paper introduces an improved of multiple harmonic sources identification that been produced by inverter loads in power system using time-frequency distribution (TFD) analysis which is spectrogram. The spectrogram is a very applicable method to represent signals in time-frequency representation (TFR) and the main advantages of spectrogram are the accuracy, speed of the algorithm and use low memory size such that it can be computed rapidly. The identification of multiple harmonic sources is based on the significant relationship of spectral impedances which are the fundamental impedance (Z1) and harmonic impedance (Zh) that extracted from TFR. To verify the accuracy of the proposed method, MATLAB simulations carried out several unique cases with different harmonic producing loads on IEEE 4-bus test feeder cases. It is proven that the proposed method is superior with 100% correct identification of multiple harmonic sources. It is envisioned that the method is very accurate, fast and cost efficient to localize harmonic sources in distribution system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Power Electronics and Drive Systems (IJPEDS)
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.