This paper introduces the accurate identification of harmonic sources in the power distribution system using time-frequency distribution (TFD) analysis, which is S-transform. The S-transform is a very applicable method to represent signals parameters in time-frequency representation (TFR) such as TFR impedance ( Z TFR ) and the main advantages of S-transform it can provide better frequency resolution for low frequency components and also offers better time resolution for high-frequency components. The identification of multiple harmonic sources are based on the significant relationship of spectral impedances ( Z S ) that extracted from the Z TFR , consist of the fundamental impedance ( Z 1 ) and harmonic impedance ( Z h ). To verify the accuracy of the proposed method, MATLAB simulations carried out several unique cases on IEEE 4-bus test feeder cases. It is proven that the proposed method is superior, with 100% correct identification of harmonic source location. It is proven that the method is accurate, fast and cost-efficient to localize harmonic sources in the power distribution system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: TELKOMNIKA (Telecommunication Computing Electronics and Control)
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.