Abstract

Ageing of large transformer fleets is a challenge for utilities. To assess the condition of existing transformer fleets, transformer oil is commonly tested for multiple parameters and the data are recorded in large databases for subsequent interpretation. Through analysing multiple databases including oil test results and individual transformer details pertaining to UK in-service transformers operating at primary voltage levels of 33, 132, 275 and 400 kV, population analyses revealed a generic early degradation phenomenon as indicated by an early peak in acidity and 2-FAL trends with in-service age. By exploring the phenomenon from manufacturer, loading and oil chemistry change perspectives, results suggested that the early degradation was most likely due to an oil chemistry change resulting from hydrotreatment oil refining method introduced in the late 1980s. Judging from the faster degradation trend of the affected transformers, a separate asset management strategy may be needed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.