AbstractWith the high penetration and flexible access of inverter‐interfaced distributed generators (IIDGs), it is gradually becoming difficult for traditional protection schemes to meet the requirements for the safe operation of distribution networks (DNs). Active protection schemes based on power electronic equipment provide a new approach. On the basis of the controllability of voltage source converters, a method for active high‐frequency signal injection and a selection principle for the corresponding control parameters are proposed. Considering the impact of T‐connected load branches on the protected line, the high‐frequency current characteristics at the three terminals during internal and external faults are analysed. On this basis, an active protection scheme based on high‐frequency current is proposed for DNs with IIDGs. The performance of the proposed scheme is verified via PSCAD/EMTDC simulation software. The test results show that the proposed scheme can reliably trip during internal faults and identify faulty phases, which has better endurance to fault resistance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.