Abstract

ABSTRACT A new algorithm for direct estimation of voltage phasor, frequency and its rate of change, of a voltage signal distorted by a DC component and contaminated by random noise is presented. The method is based on the non-recursive Least Error Squares Technique (LS Technique). Using digitized samples of voltage at the relay location, the estimation of the voltage signal unknown parameters is improved by means of an update procedure. The algorithm is adapted to the actually estimated frequency iteratively, which improved the measurement accuracy, increased the measurement range and reduced sensitivity to the noise. To demonstrate the performance of the algorithm developed, computer simulated data record tests are presented. The proposed method seems to be particularly useful in the field of frequency relaying.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.