Abstract

AbstractPartial discharge (PD) detection on live UHVEHV power cables and accessories is one of the most important techniques to prevent cable systems from serious difficulties caused by slight errors in joining the cables. A new PD detecting method is proposed in this paper. A resonance‐type partial discharge (REDI) sensor is developed for detecting PD occurring inside the joints of live XLPE insulated cables. This sensor picks up the high‐frequency components of PD current pulses on the surface of live cables, hence the output signals can clearly be observed at the noiseless area (for example, 10‐60 MHZ).This new method was applied to the initial ac breakdown tests with three different types of joints of UHV/EHV power cables. The PD pulse sequence was detected before their breakdown in all cases. The charge quantity and the number of pulses increased tremendously just before the breakdown. In addition, the phase of PD pulse against the applied voltage (ϕ‐q characteristics) changes with time or with the progress of deterioration. According to these experimental results, the REDI sensor can be applied to the insulation diagnosis of live power cable joints.