Abstract
Partial discharge (PD) detection in withstand voltage test is different from that under operation voltage for after-laying cable circuit. For large-scale XLPE cable circuit of 15km, a special distributed PD detection in-sync testing system was created for the withstand voltage test of 500kV (1.7Uo/1Hr), HFCT PD sensors were distributed and installed at every cable joint and cable termination. To localize a PD where and when it is just detected between any two neighboring PD sensors on a cable, all local signal process units are made to work synchronously, and the communication system is constructed by optical fiber cable. To ensure the high quality examination, measurement of PD propagation velocity of cable, frequency characteristics, and calibration with injection by PD simulated pulse generator were conducted onsite before test. This paper also shows some print-screen photos from the practical test to tell how the corona and the other background noise signals can be distinguished by the detected original signal waveform, selecting detection frequency filters, and the time differential identification unit. It should be a valuable reference case.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.