Abstract
Partial discharges (PD) detection is an effective method to evaluate the insulation condition of power cable joint. However, optimization of the partial discharge sensor was hard to be achieved because of the complex nature of cable joint. In this paper, the waveform and frequency characteristics of the partial discharge pulse in power cable were studied with experiment firstly. Then, the partial discharge pulses were numerical modeled to be used as excitation in cable joint simulation model. Furthermore, an electromagnetic simulation method of PD propagation in cable joint with considering the frequency dependent dielectric parameter was proposed. Afterwards, the quantitative relation between the sensor sensitivity and the sensor structure was discussed based on the developed pulse model and cable joint model. Calculations and measurements indicated the numerical sensor design can be achieved with the proposed pulse numerical model and cable joint simulation method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Dielectrics and Electrical Insulation
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.