Abstract

Downed distribution conductors in overhead distribution systems may not be a concern for equipment but greatly challenge the safety of persons, as well as the integrity of properties. Standard overcurrent protective devices may not be able to detect the magnitudes of currents resulting from high-impedance ground faults. Sophisticated relays able to detect high-impedance ground faults have been available to electric utilities. However, their implementation is rather uncommon, especially in developing countries, most likely due to their costs. In this paper, the authors formalize the problem, and propose a possible cost-effective solution for low-voltage overhead lines with neutral wire. This solution consists of a metal hook underneath the line conductors, attached to the pole and connected to the neutral wire. In the case of a falling line, the hook would be contacted and a line-to-neutral short circuit would occur; this would positively activate existing standard overcurrent devices, which can therefore disconnect the supply. Costs related to the installation of the device to existing overhead lines are herein analyzed. The effectiveness of the proposed solutions for two different voltage levels (400 V in European countries and 240 V in the USA) is also discussed.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.