Abstract
This paper aims to develop a coordinated controller to enhance the low voltage ride through (LVRT) performance of a permanent magnet synchronous generator (PMSG) based variable speed wind energy conversion system (WECS). This coordinated control comprises of a pitch angle control, a flux weakening control and a static synchronous compensator (STATCOM) control. The pitch angle control is adjusted to smooth the WECS output power fluctuations or to enhance the LVRT performance. The flux weakening controller is used to reduce the overvoltage of DC-link capacitor, and the STATCOM control is used to ensure continuous operation of WECS during symmetrical and asymmetrical grid faults. The proposed coordinated control method is compared with the conventional LVRT strategy based on the braking chopper (BC) via time series simulation results and effectiveness of the proposed control is verified.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have