Abstract

It is well known that the flow distribution in data centers can be effected by a variety of parameters such as rack and computer room air conditioning (CRAC) positions, raised-floor height, ceiling height, and percentage opening of perforated tiles. In the present paper, numerical simulations are conducted to optimize the layout of a raised-floor data center with respect to these parameters. Two different approaches have been used: parametric optimization; and a multivariable approach using response surface optimization. In the parametric optimization procedure, the data center is optimized with respect to the maximum temperature in the room. While in the multivariable approach, a cost function is constructed from all the rack inlet temperatures and is minimized. The results show that the multivariable approach is computationally economical and the optimized layout gives a better thermal performance compared to that of parametric optimization.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.