AbstractIn this paper, the concept of analog filter circuit is used for designing of wide area damping controller (WADC) in power system. The designed continuous mode filter based WADC is robust enough to deal with the problem of imperfect communication medium, which include process noise, measurement noise and signal latency in wide area remote signal. Residue method is used for the selection of wide area control signal and controller location. Modelling of imperfect communication network is done using Pade approximation and by inserting Gaussian random noise. The effectiveness of filter based WADC as a power system stability agent is assessed in the frequency domain using two typical test power systems and via appropriate time domain simulations based upon the non-linear model on MATLAB/Simulink software platform.