In Iran most of the electricity is generated by thermal power plants. As a result of fuel oil burning in winter time, the air heaters of the boilers have to be washed and cleaned frequently. The wastewater originating from air heater washing is then treated in an effluent treatment plant by chemical precipitation followed by dewatering of the sludge produced. The resulting waste is classified as specific industrial waste that should be characterized in detail under the Waste Management Act of Iran. The quantity of this waste produced in the studied power plant is about 20 tonnes year(-1). In the present investigation, the first to be carried out in Iran, seven composite samples of dewatered sludge from air heater washing wastewater treatment were subjected to investigation of the physical properties, chemical composition and leaching properties. The most likely pollutants that were of concern in this study were heavy and other hazardous metals (Cd, Co, Cr, Mn, Ni, Pb, Zn and V). The results revealed that mean pH, wet and dry density and moisture content of the waste were 6.31, 1532 kg m(-30, 1879 kg m(-3) and 15.35%, respectively. Magnetite, SiO2, P2O5, CaO, Al2O3 and MgO were the main constituents of the waste with a weight percentage order of 68.88, 5.91, 3.39, 2.64, 2.59 and 1.76%, respectively. The toxicity characteristic leaching procedure test results for some heavy and other hazardous metals showed that mean elemental concentrations of Cd, Co, Cr, Mn, Ni, Pb, V and Zn in leachate were 0.06, 1.55, 5.49, 36.32, 209.10, 0.58, 314.06 and 24.84 mg L(-1), respectively. According to the Waste Management Act of Iran this waste should be classified as hazardous and should be disposed of in accordance with hazardous waste disposal regulations.
Read full abstract