Gas fields differ from industrial enterprises by long power transmission lines with low electrical loads (low density), which grow many times during the life cycle. Power supply to gas well clusters is carried out according to the scheme - “main circuit with one through line with transformer substations distributed along the line”. The distribution of transformer substations along the transmission line affects the voltage loss, and, consequently, the choice of voltage class. The purpose of the research is to quantify the distribution of transformer substations along the power line to develop a mathematical model for calculating the optimal voltage class. To achieve this goal, the following tasks are solved: five power supply schemes are built for gas well clusters; electric moments are calculated for each scheme; the load distribution coefficient is determined. The problems were solved using an experimental-theoretical method (analysis and synthesis) and a software product – Mathcad. As a result, the coefficient is calculated in the work - for even load distribution, when placing the entire load at the end of the line and when placing the load at the beginning of the line.