This article discusses the breakdown voltage characteristics of gas‐filled transformers and reactors. To determine their insulation characteristics, this study has used models simulating their insulating elements: interturn and section‐to‐section insulation. The study measured 50% breakdown voltages in the section‐to‐section and interturn models under standard lightning impulse voltages that were 1.13 and 1.06 times higher than those under the standard switching impulse voltages, respectively. The mechanism of the above‐mentioned facts is discussed, in terms of the formative time lag of the discharge. © 2020 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.