When a single-phase ground fault occurs near the zero or maximum point, the fault line selection of resonance grounding system is not sensitive enough. After analyzing the transient current and line impedance characteristics of zero sequence network, and making full use of the decaying DC component, power frequency component and high frequency component of the transient zero sequence current of the feeder, a fault line selection method based on correlation analysis of zero sequence current and bus zero sequence voltage derivative in high and low frequency band is proposed. The effectiveness of the method is verified by the examples from the aspects of fault closing angle, transition resistance.