AbstractThe activation of safety valves causes the development of flow reaction forces that have to be transferred in an adequate way via the piping to the steel structure or via the connected vessel into the foundation. If the safety valve outlet piping is connected to a blowdown system or, in case of blowing off into the atmosphere, are equipped with a T‐piece at the outlet, the stationary reaction forces are compensated completely. The transient opening process, however, develops flow reaction forces which culminate in peaks of short duration. In this article, a simple method will be proposed for the estimation of the resulting reaction forces as a function of the length of the pipe at the safety valve outlet. CFD calculations and blowdown tests executed with a full‐lift safety valve have confirmed this method on principle. Special importance is attributed to the short duration of the effect of the reaction forces which seems to have only a negligible impact on the supporting steel structure.
Read full abstract