In order to analyze the energy consumption and operation characteristics of the variable refrigerant flow (VRF) air-conditioning system on small time scale and put forward effective energy-saving suggestions, the VRF system operation experiments are carried out under different indoor set temperatures, different indoor unit opening quantities and different indoor set air velocities. This experiment studies the main influencing factors of energy consumption and operation of the VRF system, such as indoor temperature difference, indoor air velocity, outdoor environment temperature and so on. The results show that the rated power of indoor unit is linearly related to the energy consumption of the VRF system. The total active power changes greatly when the VRF starts and stops, and the outdoor ambient temperature changes. The indoor set air velocities have a great influence on the energy consumption and operation of the VRF system. The performance parameters increase first and then decrease with the increase of compressor frequency and load rate. When the load rate is 40 %∼60 %, the performance parameters can reach 3.2 ∼ 4.2.