To investigate the effects of high temperature and carbon fiber-bar reinforcement on the dynamic mechanical properties of concrete materials, a muffle furnace was used to treat two kinds of specimens, plain and carbon fiber-bar reinforced concrete, at high temperatures of 25, 200, 400 and 600 °C. Impact compression tests were carried out on two specimens after high-temperature exposure using a Hopkinson pressure bar (SHPB) test setup combined with a high-speed camera device to observe the crack extension process of the specimens. The effects of high temperature and carbon fiber-bar reinforcement on the peak stress, energy dissipation density, crack propagation and fractal dimension of the concrete were analyzed. The results showed that the corresponding peak strengths of the plain concrete specimens at 25, 200, 400, and 600 °C were 88.37, 93.21, 68.85, and 54.90 MPa, respectively, and the peak strengths after the high-temperature exposure first increased slightly and then decreased rapidly. The mean peak strengths corresponding to the carbon fiber-bar reinforced concrete specimens after high-temperature action at 25, 200, 400, and 600 °C are 1.13, 1.13, 1.21, and 1.19 times that of plain concrete, respectively, and the mean crushing energy consumption densities are 1.27, 1.31, 1.73, and 1.59 times that of plain concrete, respectively. The addition of carbon fiber-bar reinforcement significantly enhanced the impact resistance and energy dissipation of the concrete structure, and the higher the temperature was, the more significant the increase. An increase in temperature increases the number of crack extensions and width, and the high tensile strength of the carbon fiber-bar reinforcement and the synergistic effect with the concrete material reduce the degree of crack extension in the specimen. The fractal dimension of the concrete ranged from 1.92 to 2.68, that of the carbon fiber-bar reinforced concrete specimens ranged from 1.61 to 2.42, and the mean values of the corresponding fractal dimensions of the plain concrete specimens after high-temperature effects at 25, 200, 400, and 600 °C were 1.19, 1.21, 1.10, and 1.11 times those of the fiber-reinforced concrete specimens, respectively. The incorporation of carbon fiber-bar reinforcement reduces the degree of rupture and fragmentation of concrete under impact loading and improves the safety and stability of concrete structures.