The Norton equivalent model based on the transfer function and the frequency domain analysis method for inverter resonance analysis lacks a comprehensive analysis of the resonant characteristics, and more information about the resonant key components and the degree of participation cannot be obtained. In this paper, a decomposed conductance model is proposed to characterize the resonance characteristics of the multi-inverter grid-connected system and the effect of the equivalent control link of the inverter on the resonance in more detail by combining the modal analysis method and the sensitivity analysis method. Firstly, based on αβ coordinates, the conductance division is carried out for the dual-loop inverter control link with the voltage external loop and current internal loop using capacitor-current feedback damping, and the inverter model based on the decomposition conductance is derived. The mathematical model of the multi-inverter grid-connected system is then established. Secondly, the resonance characteristics of the system are analyzed by combining the modal and frequency domain analysis methods when the number of inverters, inverter parameters, and grid-side impedance are changed. Thirdly, the degree of involvement of the system components, especially the equivalent control link of the inverter in resonance conditions, is determined in combination with the proposed model and the sensitivity analysis method, which is the basis for proposing an effective suppression strategy. Finally, a simulation model is built to verify the proposed method and the analysis results.