In power systems, analysis of critical faults, mainly, different types of simultaneous faults on transmission lines, is a sensitive issue. To identify the accurate fault place during a simultaneous fault condition, all major algorithms fail to provide the desired results. In this paper, an analysis of simultaneous faults called broken and fallen to earth conductor fault conditions is carried out. With the help of an equivalent sequence components network, generalized impedance equations are derived to determine the accurate fault place on the transmission line during the simultaneous broken and fallen to earth conductor’s fault condition. For authentication of the derived method, simulation has been done using MATLAB tool with two different medium transmission lines. Simulation outputs manifest the accuracy of the proposed generalized impedance equations by showing 98% accuracy for identifying precise fault places. The derived fault analysis method uses the sequential network formation technique, which can be easily understood by researchers.