A new experimental-theoretical approach to the toxic gases concentrations assessment in case of fire indoors is offered. The analytical formulas for calculation of CO average volume density are received. These formulas do not contain the geometrical sizes of the room and surfaces dimensions of combustible materials and, therefore, are valid under conditions of as a small-scale fire as a large-scale fire. A small-scale experimental installation for modeling fire thermal and gas dynamics in the closed or open thermodynamic system has been designed. The results of the experiments on determining dependencies of CO average volume density from average volume temperature and oxygen average volume density as well as dependencies of specific coefficients of CO emission and specific mass rates of the combustible material gasification from the time of tests during the burning of wood, transformer oil and PVC cables shield are presented. The results of numerical experiments on CO density calculation in small and large scale rooms using the proposed analytical solutions, integral, zone and field models for calculation of fire thermal and gas dynamics are presented. The comparison with the experimental data obtained by the authors and given in the literature has been performed. It is shown that CO density calculation in the full-scale room at the incipient stage of the fire can be carried out taking into account only the experimental dependences of CO from temperature or O2 density, that have been obtained from small-scale experiments. Therefore the solution of the equation of carbon monoxide mass conservation law is not necessary.