Abstract

The objective of this paper is to provide the reliable calculation procedure for determining heat and mass flow rates for plate finned tube heat exchangers in dehumidification regimes that can be used easily in engineering practice. For this purpose, the experiments are conducted on two heat exchangers, and datasets for six more heat exchangers are used from literature. Comprehensive database is established with total of 637 sets of data, and it gathers 365 new measurement sets and 272 sets from open literature. The new calculation procedure predicts heat transfer rate and condensate flow rate where new methodology approach (based on the porous velocity, the ratio of characteristic surfaces and hydraulic diameter) is used. Predicted results show 5 to 10 % deviation for heat duty and up to 20 % for mass flow rate from experimental results, which is of importance to industrial practice.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call