Abstract

ABSTRACT Mixing and renewal processes are crucial for maintaining adequate drinking water quality in storage tanks. This paper studies the influence of baffle structures and of fill-and-draw cycles on water mixing and renewal in rectangular cross-section tanks through laboratory tracer tests carried out in two small-scale tanks (with and without baffles) and compares with results from a full-scale test. This study shows that the use of baffles inhibits water mixing and keeps older water pockets in small recirculation zones, though baffles allow faster water renewal than in open tanks for lower flow rates. High water volume variation in fill-and-draw cycles (between 50% to 80%) promotes water renewal, independently of the tank configuration (i.e. cross-section and the existence of baffles). Despite the existing baffle structure in the full-scale rectangular tank with 20% water volume variation, the high flow rates allowed a rapid renewal of the stored water.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.