Abstract

<p class="Abstract">In this paper, we have presented a simulation study to analyze the power quality of three phases medium voltage grid connected with distribution generation (DG) such as photovoltaic (PV) farms and its control schemes. The system uses two-stage energy conversion topology composed of a DC to DC boost converter for the extraction of maximum power available from the solar PV system based on incremental inductance technique and a three-level voltage source inverter (VSI) to connect PV farm to the power grid. To maintain the grid voltage and frequency within tolerance following disturbances such as voltage swells and sags, a fuzzy logic-based Dynamic Voltage Restorer is proposed. The role of the DVR is to protect critical loads from disturbances coming from the network. Different fault conditions scenarios are tested and the results such as voltage stability, real and reactive powers, current and power factor at the point of common coupling (PCC) are compared with and without the DVR system.</p>

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call